JOB ESTIMATOR GUIDE

 

Each POWERWALL unit  is  48 inches long and 12 inches high. 

 1. Calculate the total number of block: 

                      Thus a 24' x 10' wall = 240sf   240/4 = 60 blocks

                  If you had a total of eight walls:

  1. 45' x 8' = 360sf

  2. 37' x 8' = 296 "

  3. 28' x 8' = 224 "

  4. 12' x 8' = 96   "

  5. 33' x 8' = 264 "

  6. 22' x 8' = 176 "

  7. 10' x 8' = 80   "

  8. 43' x 8' = 344 "

                    Total SF = 1840 / 4 = 460 block

2.  Determine takeoff for openings for door and windows:

                example:   1 Garage dr. @  20' x 7'  = 140sf

                                     1 Front dr.   @  5' (2 dr.) =  36sf

                                     2  Ext drs. @  3.0'  = 46sf

                                     2  Sl. Glass drs. @ 6.0' (2 panel)= 70sf

                                     1  Sl. Glass dr.  @ 9.0'  (3 panel)=  63sf

                                     5 #25 Windows @ 38" x 65" =  85sf

                                     Total square footage takeoff =  440sf

                    Total Takeoff = 440/(2/3) = 294sf

                                                        294 / 4 = 73 blocks.

                    Total block =   1840sf - 294sf = 1546sf / 4 = 387

                                                     or  460 - 73 = 387 

3.  Concrete requirements:  total sf. - takeoff sf divided by 65

                                        (1840 - 440) / 65 = 21.5 cu. yds.

 

4. Steel placement: Rebar requirements as per P.E. plans/drawings and local building code requirements.